Cummins/Onan 1750DQKB — Drying the Windings

Repair & overhaul · generator windings

For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC

Before you start

  • Voltage must begin at zero volts and be gradually increased or equipment damage will result.

Procedure

  1. Remove electronics box cover; remove connector 10 from regulator output module.
  2. Disable generator excitation using InPower service tool (set Excitation Disable Override to Excitation Off).
  3. Skip to running generator fan, or bolt generator three-phase output terminals together.
  4. Connect positive lead to connector 10-6 (X, red wire) and negative lead to 10-3 (XX, brown wire) of a variable 12 VDC source.
  5. Attach clamp-on ammeter; set 12 VDC source to zero, start set, slowly increase excitation to highest current without exceeding rating.
  6. Run genset approximately one hour, then repeat insulation resistance tests; continue drying if indicated.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Run genset approximately one hour

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.