Home›Repair guides›Cummins/Onan›Bus Voltage Calibration (C)

Cummins/Onan 1750DQKB — Bus Voltage Calibration (C)

Adjustments · PowerCommand control display

For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC

Procedure

  1. Display the Bus Voltage Calibration submenu.
  2. With all gensets OFF, attach a calibrated voltmeter to TB1-A (L1) and TB1-B (L2) of the bus PT module.
  3. Start another genset, allow it to reach normal speed and voltage, and connect operating genset to the bus.
  4. Calibrate the Bus Volts L1 reading so the display matches the calibrated meter.
  5. Shut the generator set OFF.
  6. Repeat steps 2 through 5 for Bus Volts L2 and L3.
  7. Exit menu to save changes.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.