Cummins/Onan 15.0 HA / 7.5 HA — Cranking Limiter Test

Testing & diagnosis

For the Cummins/Onan 15.0 HA / 7.5 HA, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. Check continuity of the heater and check for heating during a starting cycle.
  2. To test circuit breaking, disconnect the generator set remote start lead (terminal 3, remote) and apply a load.
  3. The start-run relay should operate immediately.
  4. After any start time delay and bilge blower time delay (begin Spec D only), the cranking limiter should heat.
  5. After 45 to 90 seconds, the limiter should open.

Specs & values

  • 45 to 90 seconds

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.