Home›Repair guides›Cummins/Onan›Checking for Proper Polarity - 2.0S-232/32C Automatic Voltage Regulator Control

Cummins/Onan 1400 / 2.0UF-232S/32 — Checking for Proper Polarity - 2.0S-232/32C Automatic Voltage Regulator Control

Testing & diagnosis · Generator field leads / control

For the Cummins/Onan 1400 / 2.0UF-232S/32, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan 1400

Before you start

  • Be sure to check for proper polarity before connecting generator field leads to control.

Procedure

  1. Connect a DC voltmeter (0-10 volts) across Al positive and A2 negative.
  2. Bring generator up to a speed between 1500 and 2500 rpm.
  3. Voltage will be very low (less than 1 volt). Al must be positive and A2 negative.
  4. If polarity is correct, proceed to connect generator to control.
  5. If polarity is backwards, see instructions for flashing the field.

Tools required

  • DC voltmeter (0-10 volts) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

Full service-parts list: Cummins/Onan 1400 →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →