Cummins/Onan 1400 / 2.0UF-232S/32 — Checking Automatic Control for Proper Polarity - 2.0S-232/32A
Testing & diagnosis · Control box terminals A1/A2, voltage regulator
For the Cummins/Onan 1400 / 2.0UF-232S/32, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan 1400
Procedure
- Remove the 60 amp cartridge type fuse from the control box.
- Connect an accurate DC voltmeter across the Al and A2 terminals in the control box with Meter '+' lead to Al and Meter '-' lead to A2.
- Slowly bring generator up to a speed between 1500 and 2500 rpm observing the voltmeter.
- If the voltmeter reads backwards check all wiring and repolarize; the reading should be 38 volts.
- Turn the voltage adjustment rheostat to give a voltmeter reading of 38 volts.
- Stop the generator, disconnect the voltmeter and reinstall the 60 ampere fuse to its clips.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 1500-2500 FridayParts $105.23 rpm
- 38 volts
Full service-parts list: Cummins/Onan 1400 →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.