Home›Repair guides›Cummins/Onan›Changing Generator Shaft Rotation - 2.0S-232/32C (Counterclockwise to Clockwise)

Cummins/Onan 1400 / 2.0UF-232S/32 — Changing Generator Shaft Rotation - 2.0S-232/32C (Counterclockwise to Clockwise)

Adjustments · Generator field / control terminals TB1

For the Cummins/Onan 1400 / 2.0UF-232S/32, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan 1400

Before you start

  • Field must always be polarized with A1 positive or regulator will be damaged.

Procedure

  1. Connect generator to control for clockwise rotation (Figure 4).
  2. Remove field lead (F1) from terminal #5 of TB1.
  3. Apply a positive 12 volt DC probe to terminal #4 of control and touch negative lead momentarily to F1.
  4. Be sure F1 is removed from control.
  5. Reconnect F1 to terminal #5 and run generator.
  6. To change back from clockwise to counterclockwise, F2 will be connected to terminal #5; repeat above steps.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • F1 removed from terminal #5 of TB1
  • Positive 12 volt DC probe to terminal #4

Full service-parts list: Cummins/Onan 1400 →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.