Home›Repair guides›Cummins/Onan›Out-Of-Service Protection (over 30 days)

Cummins/Onan 12.0 RDJC — Out-Of-Service Protection (over 30 days)

Maintenance · Generator set

For the Cummins/Onan 12.0 RDJC, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan RDJC

Before you start

  • Use a trickle charger to maintain battery specific gravity during storage.

Procedure

  1. Run set until thoroughly warm under at least 50 percent load.
  2. Shut down the engine.
  3. Disconnect starting batteries and follow standard battery storage procedures.
  4. Drain oil while warm; refill with clean oil and attach a caution tag.
  5. If exposed to freezing temperatures, drain coolant from engine, water pump and cooling system components.
  6. Remove flexible exhaust section and plug the engine exhaust outlet; attach warning tag.
  7. Service air cleaner.
  8. Remove glow plugs, pour 1 ounce rust inhibitor (or SAE #10 oil) into each cylinder, crank several times, reinstall glow plugs.
  9. Check fuel filters for presence of water.
  10. Clean throttle and governor linkage and protect with a clean cloth.
  11. Clean and wipe entire unit; coat rust-susceptible parts with light oil or grease.
  12. Provide a suitable cover for the entire unit.

Specs & values

  • 1 ounce rust inhibitor per cylinder

Full service-parts list: Cummins/Onan RDJC →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.