Cummins — Air Cleaner Cartridge Installation
For these Cummins models: $S338/QE338 A/C Models, Compleat, M11, M1i Series Engines, ps200da.
Browse Cummins generators & specs →
Before you start
- Care must be taken to keep the cleaner face unobstructed.
Procedure
- Hold the cartridge in the same manner as when removing it from the housing.
- Insert the clean cartridge into the housing.
- Avoid hitting the cartridge tubes against the sealing flange on the edges of the air cleaner housing.
- Firmly press all edges and corners of the cartridge with your fingers to effect a positive air seal against the sealing flange of the housing.
- The cartridge must not be pounded or pressed in the center to seal.
- Replace the pre-cleaner panel and tighten the wing nuts by hand.
- For final tightness, turn the wing nuts 1 to 1-1/2 turns with a small adjustable wrench.
- On a pre-cleaner with an exhaust aspirator, assemble the aspirator tube to the pre-cleaner panel and tighten the u-bolt.
- Reset the mechanical inlet air restriction indicator.
Tools required
- Small adjustable wrench
Source: manual:Cummins Diesel M11 Manual 1995 (2).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.