Champion 100515 — Return to Service after Storage
Operation · Generator
For the Champion 100515, from the Champion operator's manual.
Before you start
- Always connect positive battery cable first
Procedure
- Make sure utility power to transfer switch is off.
- Engine control module switch and ATS control module switch in OFF position.
- Check engine oil level; add if needed.
- Recharge batteries to 100% state of charge; replace if won't fully charge.
- Connect positive battery cable first, then negative.
- Clean and wipe down generator.
- Turn fuel shutoff valve to ON.
- Turn engine control module switch to manual; run engine 15 minutes to warm up.
- Verify no active fault codes.
- Turn engine control module switch to OFF to shut off engine.
- Turn ATS module switch to AUTO.
- Turn on utility power to transfer switch.
- Turn engine control module switch to ATS position.
- Set the exercise time.
Source: Champion operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.