Champion 100237 — Return to Service After Storage
Maintenance · Generator
For the Champion 100237, from the Champion owner's manual.
Before you start
- Always connect positive (+) battery cable first
Procedure
- Verify utility power to transfer switch is off.
- Verify engine control module and ATS control module switches are OFF.
- Check engine oil level; add if needed.
- Recharge batteries to 100% state of charge; replace if they will not fully charge.
- Connect positive (+) battery cable first, then negative (-).
- Clean and wipe down generator with mild soap and water.
- Turn fuel shutoff valve ON.
- Turn engine control module switch to MANUAL; run engine 15 minutes to warm up.
- Verify no active fault codes.
- Turn engine control module switch OFF, then ATS module switch to AUTO.
- Turn on utility power to transfer switch; verify utility LEDs lit.
- Turn engine control module switch to ATS.
- Set the exercise time.
Source: Champion owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.