Champion 100199 — Return to Service after Storage
Maintenance · Generator
For the Champion 100199, from the Champion owner's manual.
Procedure
- Make sure utility power to transfer switch is off
- Verify engine control module and ATS switches OFF
- Check engine oil level, add oil if needed
- Recharge batteries to 100% state of charge, replace if won't fully charge
- Connect positive battery cable first, then negative
- Clean and wipe down generator with mild soap and water
- Turn fuel shutoff valve to ON
- Turn engine control module to manual, run engine 15 minutes to warm up and pressurize fuel system
- Verify no active fault codes
- Turn engine control module to OFF
- Turn ATS module to AUTO position
- Turn on utility power to transfer switch
- Turn engine control module to ATS position
- Set exercise time
Source: Champion owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.