Caterpillar VR6 — Voltage Adjustment Range - Calibrate

Adjustments · VR6 voltage regulator

For the Caterpillar VR6, from the Caterpillar service manual.

Browse Caterpillar generators & specs →

Before you start

  • Do not operate generator at a voltage greater than 5% above the name plate rating.

Procedure

  1. Remove the seal from the factory calibration adjustment.
  2. Start the genset.
  3. Run the genset at no load.
  4. Turn the factory calibration adjustment fully counterclockwise.
  5. Turn the voltage adjust rheostat fully clockwise.
  6. Slowly turn the factory calibration adjustment clockwise until voltage on 20-22-24 is 252 ± 1 VAC for 60 Hz (226 ± 1 VAC for 50 Hz).
  7. Turn the voltage adjust rheostat counterclockwise.
  8. Verify that voltage on 20-22-24 is between 156 VAC and 180 VAC. The unit is calibrated.
  9. Seal the factory calibration adjustment.

Specs & values

  • 60 Hz: 252 ± 1 VAC on terminals 20-22-24
  • 50 Hz: 226 ± 1 VAC on terminals 20-22-24
  • Calibrated check: 156 VAC to 180 VAC on terminals 20-22-24

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.