Caterpillar VR6 — Exciter Field - Flash (Static Flashing)

Repair & overhaul

For the Caterpillar VR6, from the Caterpillar service manual.

Browse Caterpillar generators & specs →

Before you start

  • Do not flash permanent magnet pilot excited (PMPE) generators. Damage to the generator set can occur.

Procedure

  1. Stop the engine.
  2. At the voltage regulator, disconnect wire F1 GEN from terminal F1 and wire F2 GEN from terminal F2.
  3. Connect the positive cable of the 6 volt source to wire F1 GEN.
  4. Momentarily put the negative cable of the 6 volt source on wire F2 GEN two or three times.
  5. Do not hold the negative cable to wire F2 GEN for more than one or two seconds.
  6. Connect all wires that were previously disconnected.