HomeRepair guidesVoltage Regulator Resistance Verification and Modification

Caterpillar — Voltage Regulator Resistance Verification and Modification

A Caterpillar service procedure — check it applies to your exact model before use.

Browse Caterpillar generators & specs →

Procedure

  1. Verify resistance does not exceed 0.25 Ohm at both primary and secondary
  2. When using combination of pre- and post-May 1984 regulators (tan and black A1s), modify newer models to electrically match earlier models
  3. Add link from center to clockwise end of droop potentiometer as shown in Figure 8

Specs & torque values

  • 0.25 Ohm maximum at both primary and secondary

Source: manual:Cat Zero Droop Volt for Par Op lekx8142.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.