Caterpillar — Poor Voltage Regulation - Troubleshoot

Testing & diagnosis · Cat Digital Voltage Regulator (CDVR)

From a Caterpillar service manual — check it applies to your exact model before use.

Browse Caterpillar generators & specs →

Procedure

  1. Verify the voltage regulator chassis is properly grounded at terminal P6-6.
  2. Check for grounded field leads; isolate from ground if found.
  3. Check for grounded PMG leads; isolate from ground if found.
  4. Verify generator frequency is not dropping below the under frequency set point when load is applied.
  5. Verify regulation is not affected by normal droop operation.
  6. Verify regulation is not affected by normal line loss compensation; replace regulator if not.
  7. On new/commissioned applications, check the PID value; reduce Kg then Kp if voltage fluctuates at steady state.

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.