Operation · Caterpillar Digital Voltage Regulator (CDVR)
From a Caterpillar service manual — check it applies to your exact model before use.
Browse Caterpillar generators & specs →
Procedure
- Apply 24 VDC control power to the voltage regulator.
- Connect the "Communication Adapter II" module between the computer and the primary "CANbus" port and start the Cat ET software. Select the appropriate communication port, if prompted.
- Wait for the software to recognize the ECM's.
- If the software does not automatically connect, click on the "CONNECT" button at the top of the screen.
- From the "Service" menu click on the "Configuration Tool" button. Select the CDVR from the list by clicking on it once.
- Verify that the CDVR is listed in the left panel under "AVAILABLE ECM(S)".
- Select the configuration group to be viewed by clicking on the group in the left panel.
- Double click the parameter in the right panel, or highlight the parameter and press "ENTER".
- Type or select the new value in the "CHANGE PARAMETER VALUE" window. Click on "OK". Click on "YES" to confirm.
- Repeat steps 7 through 9 for each parameter to be programmed.
- Click the "DISCONNECT" button to disconnect communication.
Tools required
- Cat ET Software Amazon
- Communication Adapter II Amazon
- IBM compatible PC with serial port, 486DX2 or faster (100 MHz or higher microprocessor recommended) Amazon
- 24 VDC control power to the voltage regulator Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.