Home›Repair guides›Caterpillar›Parallel Operation - Voltage Adjustment

Caterpillar — Parallel Operation - Voltage Adjustment

Adjustments · Voltage Regulator

From a Caterpillar owner's manual covering: 7C-1000, 9Y-1300, 9Y-1400, SR4. Check it applies to your exact model before use.

Applies to: Caterpillar SR4

Before you start

  • Damage to the generator is possible. Do NOT exceed rated ampere load on any single generator.

Procedure

  1. Adjust voltage as described for Single Unit Operation, Initial Start-Up.
  2. With the engine running at rated speed, turn the voltage droop clockwise about 1/2 of full range.
  3. Readjust the voltage level control until the voltage is about 5% above desired voltage.
  4. Apply full load.
  5. Readjust the voltage droop control to obtain desired voltage with full load at 0.8 power factor.
  6. Repeat Steps 3, 4 and 5 for each generator to be paralleled until line voltage is equal to desired level at full load and no load voltage is approximately 5% above rated voltage.
  7. Parallel generators and apply the driven load; adjust voltage droop controls to share current proportionally.
  8. Make final adjustments after paralleled generators have been running at full load for one hour or more; tighten locknuts and install the access cover.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Loads of 0.8 power factor require a generator voltage droop of about 5%
  • Voltage droop clockwise about 1/2 of full range

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.