Caterpillar — No Voltage - Troubleshoot

Testing & diagnosis · Cat Digital Voltage Regulator (CDVR)

From a Caterpillar service manual — check it applies to your exact model before use.

Browse Caterpillar generators & specs →

Before you start

  • Electrical shock/electrocution hazard; service by trained personnel only.
  • Terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed.

Procedure

  1. Verify all wiring is properly connected per wiring diagrams.
  2. Verify generator is running at rated speed.
  3. Determine if regulator is PMG powered or shunt powered.
  4. Check for correct input power to the voltage regulator per Electrical specification.
  5. Verify residual voltage applied to power input is at least 6 VAC; flash generator field if not.
  6. Verify fuses are not open; replace any open fuses.
  7. Verify CDVR is connected to 24 VDC control power.
  8. Verify common alarm/Shutdown LED is not flashing; if flashing, check for protective shutdown fault.
  9. If EDM (Exciter Diode Monitor) fault occurred, check rotating exciter diodes for open/shorted diodes.
  10. If over excitation fault occurred, check generator/load for fault and check for loose sensing connections.
  11. If loss of sensing fault occurred, check for loose/open connections to voltage sensing inputs.
  12. If field over current fault occurred, check generator/load conditions and connections.
  13. If internal memory failure fault occurred, reset regulator; replace if fault recurs.
  14. If internal watchdog failure fault occurred, reset regulator; replace if fault recurs.
  15. Replace the voltage regulator unit if prior steps do not correct the problem.

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.