Caterpillar — No Voltage Droop - Troubleshoot

Testing & diagnosis · Cat Digital Voltage Regulator (CDVR)

From a Caterpillar service manual — check it applies to your exact model before use.

Browse Caterpillar generators & specs →

Procedure

  1. Verify the voltage regulator is programmed for droop mode.
  2. Verify the droop setting is not adjusted to 0%; increase above 0% if so.
  3. Check for an open circuit at terminals P12-1, P12-2 and CT2.
  4. Verify connections are correct and CT/PT are not installed backwards or on the wrong phase.
  5. Verify the test load is not purely resistive; apply an inductive load and retest.
  6. Verify the current sensing transformer is compatible (regulator has a 5 A CT input).
  7. Check wiring to the programmable switch input if configured for line loss compensation.
  8. Replace the voltage regulator if all prior steps fail to correct the malfunction.

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.