Caterpillar — No Line Loss Compensation - Troubleshoot
Testing & diagnosis · Cat Digital Voltage Regulator (CDVR)
From a Caterpillar service manual — check it applies to your exact model before use.
Browse Caterpillar generators & specs →
Procedure
- Verify the voltage regulator is programmed for line loss compensation.
- Verify the line drop setting is not adjusted to 0%; increase above 0% if so.
- Check for an open circuit at terminals P12-1, P12-2 and CT2.
- Verify all connections are correct per the wiring diagrams.
- Verify the test load is not purely resistive; apply an inductive load and retest.
- Verify the current sensing transformer is compatible (regulator has a 5 A CT input).
- Check wiring to the programmable switch input if configured for line loss compensation.
- Replace the voltage regulator if all prior steps fail to correct the malfunction.
Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.