Caterpillar — Improper PF Regulation or KVAR Regulation - Troubleshoot
Testing & diagnosis · Digital Voltage Regulator
From a Caterpillar service manual — check it applies to your exact model before use.
Browse Caterpillar generators & specs →
Procedure
- Stop the generator set and check the wiring; if CT or PT polarity is incorrect, reverse the polarity.
- Start the generator set and load with 25% to 50% of rated load using 0.8 power factor inductive load if possible.
- Check the values in parameters :04 and :05; measure the ampere load on the B phase and the signal voltage level at terminals 5 and 6.
- Compare parameter :52 to actual generator current; slowly decrease or increase parameter :05 until the currents match.
- On 130-xxxx and older units check parameters :16 and :17; on 155-xxxx and newer units check parameters :36 and :37; try the default settings.
- If the problem only exists at low power levels, check parameter :38 and try raising the value.
- Remove the remote PF/KVAR adjust rheostat and retry. Verify CT sizing: no more than 5 VAC (RMS) at full rated load but not less than 3.5 VAC.
- Disconnect accessory wiring from terminals 3, 5, 6, 7, 40, 41, 42, 43, 44, 45, and 50 and operate at no load to isolate a faulty accessory.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Droop current transformer: 3.5 to 5 VAC (RMS) at full rated load
Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.