Caterpillar — Generator Set - Test

Testing & diagnosis

From a Caterpillar owner's manual covering: C3.3, C3.3 Rental Generator Set, C4.4, C4.4 Rental Generator Set, D4D1-Up, GLE1-Up, N3X1-UP, N4R1-Up, N4X1-Up, X3B1-UP, XYC1-Up, XYD1-Up. Check it applies to your exact model before use.

Applies to: Caterpillar C3.3, Caterpillar C4.4

Before you start

  • Personal injury or death can result from high voltage
  • Make sure the unit is off-line, locked out or tagged DO NOT OPERATE
  • Make sure all capacitors are discharged

Procedure

  1. Stop the generator. Connect the potential transformer's high voltage winding to generator terminals T1 and T2.
  2. Connect the voltmeter to the low voltage winding. Connect a second transformer to T1 and T3 if available.
  3. Connect the secondary terminals corresponding to T2 of both transformers together.
  4. Disconnect wires "E+" and "E-" from the voltage regulator. Disconnect the generator from the load.
  5. Connect a 12 VDC automotive battery to wires "E+" and "E-".
  6. Measure AC voltage across low voltage terminals for T1-T2, T2-T3 and T3-T1. Record the voltages.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Perform the test with the generator set under load

Full service-parts list: Caterpillar C3.3 →, Caterpillar C4.4 →

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.