Caterpillar — Generator Overcurrent - Troubleshoot
Testing & diagnosis · Cat Digital Voltage Regulator (CDVR)
From a Caterpillar service manual — check it applies to your exact model before use.
Browse Caterpillar generators & specs →
Procedure
- Verify potential transformers are installed correctly.
- Check for a difference between sensed voltage and rated voltage from the wye center tap.
- Verify Rated voltage, PT primary, and PT secondary parameters equal generator rated voltage.
- Verify field winding inputs to the CDVR are not partially or fully shorted.
- Check exciter for proper resistance value.
- Replace the voltage regulator if all prior steps fail to correct the malfunction.
Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.