Home›Repair guides›Caterpillar›Generator Bearing Temperature - Test/Record

Caterpillar — Generator Bearing Temperature - Test/Record

Maintenance

From a Caterpillar owner's manual covering: C3.3, C3.3 Rental Generator Set, C4.4, C4.4 Rental Generator Set, D4D1-Up, GLE1-Up, N3X1-UP, N4R1-Up, N4X1-Up, X3B1-UP, XYC1-Up, XYD1-Up. Check it applies to your exact model before use.

Applies to: Caterpillar C3.3, Caterpillar C4.4

Before you start

  • A generator set should never operate above the recommended set points

Procedure

  1. Measure bearing temperature after generator reaches normal operating temperature.
  2. RTDs are 100 ohm; EMCP 3.2/3.3 may be configured to ALARM or SHUTDOWN.
  3. An alarm is activated at 85 C (185 F).
  4. A shutdown occurs at 95 C (203 F).
  5. Bearing temperatures can also be recorded with an infrared thermometer.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Alarm at 85 C (185 F)
  • Shutdown at 95 C (203 F)

Full service-parts list: Caterpillar C3.3 →, Caterpillar C4.4 →

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.