Home›Repair guides›Caterpillar›Fault Identification

Caterpillar — Fault Identification

Testing & diagnosis · Digital Voltage Regulator

From a Caterpillar service manual — check it applies to your exact model before use.

Browse Caterpillar generators & specs →

Before you start

  • When a shutdown fault code is reset, the digital voltage regulator will begin operation again. If the generator is being driven, it will begin to regulate according to engine/generator speed.

Procedure

  1. Check the excitation: use a multimeter set for VDC across exciter field outputs F1 and F2, or view parameter :55.
  2. If regulator is providing excitation go to step 2; if not, go to step 4.
  3. Check alarm status: display flashing or alarm output off means an alarm is active. Go to step 5; otherwise go to step 3.
  4. Check if a new alarm has been logged in parameter :92. If yes, troubleshoot using that code; if no, STOP.
  5. Check fault status: display flashing or fault output off means a shutdown fault is active. Go to step 5; otherwise see Troubleshooting.
  6. Check shutdown fault log parameter :92. Number starting with 6 is an alarm; 7 is a resettable shutdown fault; 8 is a non-resettable shutdown fault; 9 is a severe fault and the unit must be replaced.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Excitation voltage at F1 and F2: 6 to 14 VDC at no load

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Caterpillar repair guides →