Caterpillar — Establishing Communication

Operation · Caterpillar PC Software / CDVR

From a Caterpillar service manual — check it applies to your exact model before use.

Browse Caterpillar generators & specs →

Before you start

  • Battery power (24 VDC) must be available at "P12-8" (B+) and "P12-7" (B-) in order for the remote communications port to operate.
  • Issuing commands while the "Please wait..." dialog box is present may disrupt communication between the PC software and the voltage regulator.

Procedure

  1. Open the voltage regulator communication port by clicking "Communications" on the menu bar, hovering the mouse pointer over "Open Comm Port" and clicking "RS-232 Port".
  2. Enter the password in the "Password" dialog box. Each voltage regulator is delivered with "cat" as the password.
  3. On the "Comm Port" screen, select "Comm 1", "Comm 2", "Comm 3", or "Comm 4" as the active communication port and click the "Initialize" button.
  4. Wait until the "Please wait..." dialog box disappears before executing communication commands.

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.