Procedure
- Ask operator about cause; if known and repaired, reset genset and resume.
- Compare Generator Overfrequency and Desired Engine Speed Request setpoints to default setpoints.
- EUI engines: verify generator output frequency can be viewed and adjusted on EMCP 3 display.
- MUI engines: adjust frequency with speed potentiometer; if not adjustable, go to step 5.
- Shut down engine; disconnect speed potentiometer from 2301A Governor terminals 11 and 12; measure resistance (0-100 ohms).
- Check speed potentiometer harness open circuit; terminal 11 and 12 to potentiometer resistance should be 5 ohms or less.
- EUI engines: check J1939 Data Link wiring between EMCP 3 and Engine ECM.
- Check three fuses on AC voltage inputs of EMCP 3; they should not be open.
- Open circuit breaker, start engine, measure line-to-line voltage at all three AC input fuses; should equal rated voltage.
- Shut down engine; remove EMCP 3 harness connector; inspect connector and wires between voltage inputs and fuses.
Tools required
- multimeter Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Speed potentiometer resistance: 0 to 100 ohms
- Harness resistance: 5 ohms or less
- Line-to-line voltage: rated voltage of genset