Before you start

  • Pressurized system: hot coolant can cause serious burns

Procedure

  1. Stop engine, allow to cool, relieve pressure at filler cap
  2. Open drains/vent plugs to drain jacket water and separate circuit
  3. Flush system with clean water to remove debris
  4. Fill with cleaner/water mixture (0.5 L cleaner per 15 L capacity)
  5. Run engine 30 min minimum with coolant at least 82 °C (180 °F)
  6. Drain cleaning solution, flush with clean water until clear
  7. Fill with coolant/antifreeze, purge air at low idle then high idle
  8. Inspect filler cap gaskets, install, start and check for leaks

Specs & values

  • Fill rate max 19 L (5 US gal) per minute
  • Cleaner ratio 0.5 L per 15 L (4 US gal) capacity

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.