Home›Repair guides›Caterpillar›Bearing Inspection

Caterpillar — Bearing Inspection

Maintenance · Generator Bearings

From a Caterpillar owner's manual covering: 7C-1000, 9Y-1300, 9Y-1400, SR4. Check it applies to your exact model before use.

Applies to: Caterpillar SR4

Before you start

  • Bearings being removed for failure analysis should not be cut off with a torch.
  • DO NOT MIX GREASES

Procedure

  1. Remove bearing bracket; inspect the bracket bore and bearing outer race and rolling elements.
  2. Inspect the bearing bracket bore for out of roundness, excessive wear, and a bracket step less than 0.0762 mm (.003 in).
  3. Spherical Roller Bearing should be cleaned and re-packed with 108-8611 Grease; pack the bearing and cavity to one-third to one-half of cavity volume.
  4. All ball bearings should be cleaned and the bracket cavity re-packed with 2S-3230 Grease to one-third to one-half of the cavity volume.
  5. Make sure the grease supply tube to the bearing is filled with grease.
  6. Remove the bracket drain plug and operate generator for one hour to force excess grease out of the cavity.
  7. Stop the engine, install the bracket drain plug and wipe off excess grease.
  8. For future greasing intervals follow the recommendation on the lubrication plate or the Maintenance Schedule; repeat Step 5 each time the bearings are greased.

Specs & values

  • Bracket step less than 0.0762 mm (.003 in)
  • Approximately 3 - 4 oz. in the bearing and 4 - 5 oz. in the cavity

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.