Home›Repair guides›Caterpillar›After Storage (Drying the Generator)

Caterpillar — After Storage (Drying the Generator)

Maintenance

From a Caterpillar owner's manual covering: 7C-1000, 9Y-1300, 9Y-1400, SR4. Check it applies to your exact model before use.

Applies to: Caterpillar SR4

Before you start

  • If an oven is used for drying, use a forced air type rather than a radiant type. Radiant ovens can cause localized overheating.

Procedure

  1. Perform an insulation resistance check of the main stator windings using a megohmmeter (megger).
  2. Energize space heaters in generator, if so equipped.
  3. Put the generator in an oven at a temperature of not more than 85°C (185°F) for four hours.
  4. Install space heaters of the same type used in marine applications to heat the windings and remove moisture.
  5. Use a canvas enclosure around the generator and heating lamps to increase the temperature; make an opening in the top for release of moisture.
  6. Send a low voltage current through the windings to increase the temperature of the windings; do not exceed 85°C (185°F).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Oven temperature not more than 85°C (185°F) for four hours
  • Do not exceed 85°C (185°F)

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.