Compatible — Idle Speed Stop Adjustment
For these models: MODEL BGD, MODEL NHD.
Procedure
- Start the genset and let it warm up for ten minutes under 1/2 to 3/4 rated load.
- Disconnect the load (check for zero amps). Pull the governor rod so that the tang on the throttle lever bears against the idle speed stop screw.
- Adjust the screw to obtain 54-56 Hz (44-46 Hz).
Specs & torque values
- No-load frequency: 54-56 Hz (60 Hz) or 44-46 Hz (50 Hz)
Source: manual:965-0500_Onan_BGD_NHD_spec_H_J-K_L-M_Mobile_Generator_Servicve_manual_11-1995.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.