Briggs & Stratton — Test 16: Measure Circuit Breaker Line-Side: Test 17: Check Alternator Rotor Winding Resistance
For these Briggs & Stratton models: 10 kW, 8 kW.
Browse Briggs & Stratton generators & specs →
Procedure
- 6. Verify that the generator circuit breaker is in the OFF (Open) position.
- 7. See Figure C3. Press and hold MANUAL on control panel to start engine. Is 240 VAC present at line
- A. Yes- Manually cycle circuit breaker. Retest. If problem persists, install new circuit breaker.
- B. No- Move to Test 17: Check Alternator Rotor Winding Resistance (step 8).