Briggs & Stratton — Test 6: Check Starter Solenoid Connection: B. No- Repair or replace main battery wiring between starter and starter relay. Retest.
For these Briggs & Stratton models: 10 kW, 8 kW.
Browse Briggs & Stratton generators & specs →
Procedure
- 23. What type of generator is being serviced?
- A. 16-20 kW Horizontal Unit- Move to step 24.
- B. 8-12 kW Vertical Unit- Move to step 30.
- 16-20 kW Horizontal Units
- 24. See Figure A12. Is battery voltage at the positive post of the starter solenoid equal to or greater than
- 9.6 VDC?
- A. Yes- Move to step 25.
- B. No- Repair or replace wiring and/or connections between battery and starter. Retest.
- 25. See Figure A13. Is battery voltage on Wire 13 at the starter relay (Wire 99 on some models) equal to
- A. Yes- Move to step 26.
- B. No- Return to step 8 (under Test 1: Check Battery Voltage Supply).
- 26. See Figure A14. Disconnect control wire (Wire 98 on some models) from spade contact at starter
- 27. Install 15 Amp fuse in control panel.
- 28. Press and hold MANUAL on control panel to crank engine.
- 29. Is DC voltage on control wire at starter solenoid equal to or greater than 9.6 VDC?
- A. Yes- Install new starter. Retest.
- B. No- Repair or replace wiring between starter relay and starter solenoid. Retest.
- 8-12 kW Vertical Units
- 30. See Figure A10. Is battery voltage at the positive post of the starter relay equal to or greater than 9.6
- A. Yes- Move to step 31.
Source: manual:Briggs_Air-CooledRepairManual80019677.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.