Briggs & Stratton — Test 3: Check Trickle Charge at Battery: Test 4: Check Trickle Charge Fuse at Control Panel
For these Briggs & Stratton models: 10 kW, 8 kW.
Browse Briggs & Stratton generators & specs →
Procedure
- 15. See Figure A4. Measure AC voltage at terminals of Connector J5. Is approximately 240 VAC present?
- A. Yes- Move to step 16.
- B. No- Return to Test 2: Check Utility Voltage Input (step 12).
- 16. See Figure A7. Set Digital Multimeter to read DC volts. Connect battery cables. Measure DC voltage
- A. Yes- Retest.
- B. No- Move to Test 4: Check Trickle Charge Fuse at Control Panel (step 17).
Source: manual:Briggs_Air-CooledRepairManual80019677.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.