Briggs & Stratton — B. No- Move to Test 14: Measure Circuit Breaker Load-Side Voltage (step 2).: Test 15: Measure Generator Voltage at Control
For these Briggs & Stratton models: 10 kW, 8 kW.
Browse Briggs & Stratton generators & specs →
Procedure
- 2. Verify that the generator circuit breaker is in the ON (Closed) position.
- 3.
- 4. See Figure C1. Set Digital Multimeter to read AC volts. Press and hold MANUAL on control panel to
- A. Yes- Move to Test 15: Measure Generator Voltage at Control Panel (step 5).
- B. No- Move to Test 16: Measure Circuit Breaker Line-Side Voltage (step 6).
Source: manual:Briggs_Air-CooledRepairManual80019677.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.