HomeRepair guidesB. No- Move to Test 14: Measure Circuit Breaker Load-Side Voltage (step 2).: Test 15: Measure Generator Voltage at Control

Briggs & Stratton — B. No- Move to Test 14: Measure Circuit Breaker Load-Side Voltage (step 2).: Test 15: Measure Generator Voltage at Control

For these Briggs & Stratton models: 10 kW, 8 kW.

Browse Briggs & Stratton generators & specs →

Procedure

  1. 2. Verify that the generator circuit breaker is in the ON (Closed) position.
  2. 3.
  3. 4. See Figure C1. Set Digital Multimeter to read AC volts. Press and hold MANUAL on control panel to
  4. A. Yes- Move to Test 15: Measure Generator Voltage at Control Panel (step 5).
  5. B. No- Move to Test 16: Measure Circuit Breaker Line-Side Voltage (step 6).

Source: manual:Briggs_Air-CooledRepairManual80019677.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.