Basler — Test Procedure
Testing & diagnosis · RDP-110 Remote Display Panel
From a Basler service manual — check it applies to your exact model before use.
Procedure
- Connect the RDP-110 test setup as shown in Figure 9.
- Apply 24 Vdc control power. The Display Panel On LED should light.
- Press and hold the Lamp Test pushbutton. All LEDs should light and the horn should sound.
- Release the Lamp Test pushbutton to reset the indicators and horn.
- Apply the 10 Hz signal.
- Press and release the Lamp Test pushbutton. Observe that the LEDs and horn annunciate in the eighteen-step sequence indicated in Figure 10.
- Press and release the Alarm Silence pushbutton to end the annunciation sequence.
- Remove the 10 Hz signal and 24 Vdc control power.
- Repeat the test with 100/120 Vac control power applied instead of 24 Vdc control power.
Tools required
- Power supply, 24 Vdc Amazon
- Power source, 100/120 Vac, 50/60 Hz Amazon
- Fuse, 1 ampere (2) Amazon
- Signal generator, 10 Hz, square wave, 5 volts peak-to-peak Amazon