Basler — System Checkout
Operation · Voltage Regulator
From a Basler service manual — check it applies to your exact model before use.
Procedure
- Start the prime mover and bring up to rated speed. If a voltage shutdown switch is used, close the switch to apply excitation.
- Verify the generator output voltage. Note conditions: overvoltage, no voltage build-up, undervoltage, voltage collapses, oscillating voltage.
- Adjust the External Voltage Adjust Rheostat for nominal generator output voltage.
- Apply a load to the generator.
- Verify that voltage regulation is within ±1%.
- Alternately remove and apply the load several times to determine if the generator voltage is stable.
Specs & values
- Voltage regulation within ±1%
Source: Basler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.