Home›Repair guides›Basler›Functional Test Procedure

Basler — Functional Test Procedure

Testing & diagnosis · RDP-110 Remote Display Panel

From a Basler service manual — check it applies to your exact model before use.

Before you start

  • To avoid personal injury or equipment damage, only qualified personnel should perform the procedures in this manual.

Procedure

  1. Connect the test setup as shown in Figure 5-1.
  2. Apply dc power.
  3. The Display Panel On LED should turn on.
  4. Press and hold the Lamp Test pushbutton.
  5. The alarm should sound and all LEDs should turn on.
  6. Release the pushbutton; the alarm and LEDs should turn off.
  7. Apply the 10 hertz signal.
  8. Press and release the Lamp Test pushbutton.
  9. Each LED and the horn should annunciate in sequence before repeating.
  10. Press and release the Alarm Silence pushbutton.
  11. The cycling indicators should stop when the Alarm Silence pushbutton is pressed.
  12. Remove the 10 Hz source and the DC power input.
  13. Repeat the above test procedure with AC power applied instead of the DC power.

Tools required

  • DC power supply, 24 volts Amazon
  • 2 each, one ampere fuses Amazon
  • Voltage source, 50/60 hertz, 100/120 volts Amazon
  • Signal generator, 10.0 hertz, 5 volts peak to peak, square wave

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Basler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.