Basler — Field Flashing

Maintenance · Generator field

From a Basler service manual — check it applies to your exact model before use.

Before you start

  • The flashing source cannot be grounded unless a power isolation transformer is used.

Procedure

  1. With prime mover at rest, apply a dc flashing source across terminals F+ and A-.
  2. Connect positive of flashing source to F+ and negative to A-.
  3. When automatic field flashing is required, use a dc source not exceeding 125 V.
  4. Interconnect circuit as shown in Figure 3-5.
  5. A series limiting resistor may be required to limit flashing current.

Specs & values

  • Flashing current typically limited to approximately 50% of no-load exciter field current

Source: Basler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.