Basler — Change Sensing Voltage Taps

Adjustments · Sensing transformer T1/T2

From a Basler service manual — check it applies to your exact model before use.

Before you start

  • Meggers and high potential test equipment must not be used.

Procedure

  1. Remove the cover if applicable.
  2. Remove 9 hex screws.
  3. Remove the printed circuit board without disconnecting the wires.
  4. Locate transformer(s) T1 for single-phase sensing units (T1 and T2 for three-phase sensing units).
  5. Move the wire factory connected to T1-120 terminal to the T1 terminal labeled with desired sensing voltage.
  6. For three-phase sensing units, also move the wire from T2-120 terminal to the T2 terminal labeled with desired sensing voltage.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Factory preset for 120 Vac sensing
  • Sensing voltages: 120, 208, 240, 416, 480, 600 Vac

Source: Basler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.