Basler — Adjust Voltage Stability R4
Adjustments · Stability adjustment R4
From a Basler service manual — check it applies to your exact model before use.
Procedure
- Loosen the locking nut on R4.
- Rotate R4 clockwise (CW) approximately 30° beyond the point that stable operation is obtained.
- Tighten lock nut on R4.
Specs & values
- Factory set in 75% rotation (CW) position
Source: Basler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.