Aurora — Slow Timer Setting Adjustment
For these Aurora models: DynaGenTM ES52, ES52.
Browse Aurora generators & specs →
Procedure
- Apply power to Start/Stop terminal # 10.
- Allow the engine to Crank and start; the Engine Running LED turns ON.
- The "Timer" LED will illuminate; measure the time that this LED remains ON.
- Increase or decrease pot setting as required. The pot resolution is 12.8 seconds/turn.
- Return to step 1 as needed.
Specs & torque values
- Pot resolution: 12.8 seconds/turn
- Adjustable range: 0-256 seconds
Source: manual:dynagen-es52-user-manual-en.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.