Aurora Generators ES52 — Step-Down Transformer Use on Speed Sensing Cable with Inverter Systems
Installation · Speed sensing cable, generator output
For the Aurora Generators ES52, from the Aurora Generators service manual.
Browse Aurora Generators generators & specs →
Procedure
- Install a small transformer between generator output and speed sensing terminals on controller.
- Transformer should be rated for 120 or 240 volts input and output about 12 VAC secondary.
- Connect secondary wires to speed sensing terminals on ES52.
- Common transformer size is 24VA.
- Avoid running AC lines from inverter in same conduit as generator output lines.
Specs & values
- Transformer input 120 or 240 VAC
- Secondary around 12 VAC
- Common size 24VA
Source: Aurora Generators service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.