Aurora Generators ES52 — Selecting the Engine Speed Range

Adjustments · DIP switches 4 and 5

For the Aurora Generators ES52, from the Aurora Generators service manual.

Browse Aurora Generators generators & specs →

Procedure

  1. Generator output: use speed range 1 (LO).
  2. Flywheel alternator: use speed range 1 (LO); refer to engine specification for number of poles.
  3. Engine alternator: use speed range 1 (LO) or 2 (HI); refer to engine specification for pulley ratio and poles.
  4. Magnetic pickup: use speed range 2 (HI).
  5. Set SW4 and SW5 per range table: LO = OFF/OFF, HI = ON/ON.

Specs & values

  • LO Crank Disconnect 12 - 140 Hz
  • LO Over-Speed 44 - 300 Hz
  • HI Crank Disconnect 60 - 4156 Hz
  • HI Over-Speed 300 - 8492 Hz

Source: Aurora Generators service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.