Home›Repair guides›Aurora Generators›Loss of Speed (During Cranking)

Aurora Generators ES52 — Loss of Speed (During Cranking)

Adjustments · DIP switch 9

For the Aurora Generators ES52, from the Aurora Generators service manual.

Browse Aurora Generators generators & specs →

Procedure

  1. Enable or disable Loss of Speed While Cranking via DIP switch 9.
  2. UP or ON position enables the function.
  3. DOWN or OFF position disables the function.
  4. Loss of speed is no speed signal for at least 3 seconds and begins 3 seconds into crank cycle.
  5. Unit shuts down and indicates flashing Over-speed LED.
  6. If configured for generator output, not enough residual voltage may be present during cranking; it is recommended to disable this feature.

Specs & values

  • Loss of speed defined as no speed signal for at least 3 seconds
  • Loss of speed begins 3 seconds into crank cycle

Source: Aurora Generators service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.