Aurora Generators ES52 — Connecting ES52 to a Transfer Switch (or Remote Device)
Installation · Remote Start Contacts RSC1/RSC2
For the Aurora Generators ES52, from the Aurora Generators service manual.
Browse Aurora Generators generators & specs →
Procedure
- Remote start contacts carry high current, up to 20A peak during starting.
- If necessary, use an external normally open relay to limit current to the remote device.
- Example: Vigilant transfer switch remote start contacts are rated at 10A, so an external relay is necessary.
Specs & values
- Remote start contacts up to 20A peak during starting
- Vigilant transfer switch contacts rated 10A
Source: Aurora Generators service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.