Aurora Generators ES52 — Adjusting Timer Duration

Adjustments · Timer pot, terminals 12 and 5, Start/Stop terminal 10

For the Aurora Generators ES52, from the Aurora Generators service manual.

Browse Aurora Generators generators & specs →

Procedure

  1. Glow Plug setting (DIP switches 7 and 8 OFF): remove wires from Timer terminal #12 and Crank terminal #5.
  2. Apply power to Start/Stop terminal #10.
  3. Measure time Timer LED remains ON.
  4. Remove power from Start/Stop terminal #10.
  5. Increase or decrease pot setting as required; pot resolution is 1.6 seconds/turn.
  6. Return to step 2 as needed.
  7. Reconnect wires to Timer terminal #12 and Crank terminal #5.
  8. Slow setting (DIP switches 7 and 8 ON): apply power to Start/Stop terminal #10.
  9. Allow engine to crank and start; Engine Running LED turns ON.
  10. Timer LED illuminates; measure time LED remains ON.
  11. Adjust pot as required; pot resolution is 12.8 seconds/turn.
  12. Return to step 1 as needed.

Specs & values

  • Glow Plug pot resolution 1.6 seconds/turn
  • Slow pot resolution 12.8 seconds/turn

Source: Aurora Generators service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.