Aurora Generators — Energize the Switch
Operation · Service entrance disconnect, generator power source breaker
From a Aurora Generators service manual covering: EGSC100ASE, EGSC200ASE, EGSC400ASE, EGSCA100ASE, EGSCA200ASE, EGSCA400ASE. Check it applies to your exact model before use.
Browse Aurora Generators generators & specs →
Before you start
- Voltages within the enclosure are capable of causing severe personal injury or death. Use extreme caution to avoid contact with energized equipment.
- Contact with energized components will cause electrical shock capable of producing severe personal injury or death.
Procedure
- With the service entrance barrier removed, use a voltmeter to measure line-to-line and line-to-neutral voltages on the line side of the circuit breaker. Confirm utility voltage is correct then replace
- Ensure the generator control selector switch is set to OFF; remove the control fuse from the generator control panel and open the generator power source circuit breaker.
- Close the service entrance disconnect circuit breaker in the switch to connect the ATS to the utility power source.
- Replace the control fuse. Position the generator control selector switch to the AUTOSTART position and close the generator power source circuit breaker.
Tools required
- Voltmeter Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Source: Aurora Generators service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.