Home›Repair guides›ASCO›Maintenance Handle Operation

ASCO — Maintenance Handle Operation

Operation

From a ASCO service manual — check it applies to your exact model before use.

Before you start

  • Do not manually operate the transfer switch until both power sources are disconnected: open both normal and emergency source circuit breakers.

Procedure

  1. Deenergize the transfer switch and verify no electrical power at terminals with a voltmeter.
  2. Remove maintenance handle from clips on left side or pole cover.
  3. Insert handle into hole in shaft on left side of operator.
  4. Move handle up or down to manually operate switch to opposite position.
  5. Return switch to Normal position; letter N adjacent to Switch Position.
  6. Remove handle and store on transfer switch in clips provided.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: ASCO service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.