Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 29 kW |
| Standby kVA | 29 |
| Emissions | Tier 3 |
| Controller | DeepSea |
| Oil capacity | 11.5 L |
| Alternator | Stamford/AvK PI144H / S1L2-K (4-pole, Class Class H insulation) |
| Voltage options | 120/240 V |
| Phase | 1 |
| Rated current | 125 A |
| Power factor | 1.0 |
| Circuit breaker | 125 A |
| Battery cranking | 900 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Max ambient | 25 °C |
| Dimensions (L×W×H) | 2626×1106×1647 mm |
| Dry weight | 1253 kg |
| Sound level | 72.0 dBA @ 7 m |
Engine
| Oil capacity | 11.5 L |
|---|---|
| Displacement | 3.2 L |
| Aspiration | naturally aspirated |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Koel 4R810NA| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Fuel filter | 0.6 liter single bowl spin-on | — | |||
| Oil filter | Spin-on filter | — |
Service specifications
2| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Temperature | Exhaust temperature at rated load | 1202 | F | at rated load |
| Temperature | Exhaust temperature at rated load | 650 | C | at rated load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Ultra-low sulphur diesel | Ultra-low sulphur diesel required |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Wildcat Roughneck Diesel 20KW?
The Wildcat Roughneck Diesel 20KW is rated 29 kW standby (29.0 kVA).
What engine is in the Wildcat Roughneck Diesel 20KW?
The Wildcat Roughneck Diesel 20KW is powered by the Koel 4R810NA engine.
What fuel does the Wildcat Roughneck Diesel 20KW use?
The Wildcat Roughneck Diesel 20KW runs on diesel.
What is the oil capacity of the Wildcat Roughneck Diesel 20KW?
The Koel 4R810NA engine in the Wildcat Roughneck Diesel 20KW has an oil capacity of 11.5 liters.
How loud is the Wildcat Roughneck Diesel 20KW?
The Wildcat Roughneck Diesel 20KW is rated at 72.0 dBA at 7 m, per the manufacturer specification sheet.
How much does the Wildcat Roughneck Diesel 20KW weigh?
The Wildcat Roughneck Diesel 20KW has a dry weight of 1253 kg (2762 lb).
What voltages is the Wildcat Roughneck Diesel 20KW available in?
The Wildcat Roughneck Diesel 20KW is offered in 120/240 V, 1-phase.
What battery does the Wildcat Roughneck Diesel 20KW use?
The Wildcat Roughneck Diesel 20KW uses 1 battery, 12 V each, 900 CCA, per the manufacturer specification sheet.
What alternator comes on the Wildcat Roughneck Diesel 20KW?
The Wildcat Roughneck Diesel 20KW uses a Stamford/AvK PI144H / S1L2-K alternator. It has 4 poles. Insulation class Class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Continuous | 2.08 | 0.55 | |
| Continuous | 50% | 4.69 | 1.24 |
| Continuous | 100% | 9.82 | 2.59 |
Available documents